PLUS Series Water to Water Heat Pump
955213SDV
955213SDV
Product Specifications
Recovery L/hr (@20°C ambient and @ 50°C rise)
3672
Heat Exchanger
Copper Tube in Tube Vented
Heating Capacity
213.46 kW
Power Input
42.56 kW
COP
5.02
Recovery @50°C Rise
3672 L/hr
Heat Exchanger Design
Shell in Tube
Maximum DHW Temperature
65 °C
Refrigerant
R134a
TPR Valve Setting (VE/RT/RW)
1000/850/700 kPa
Max Water Pressure Supply without ECV (VE/SS)
800/680/560 kPa
Maximum Water Supply Pressure
660
Electrical Connection Power Supply
3 Phase / 380-415V / 50 Hz
Max Current per Phase (heat pump running, excl pump)
120.3 Amps
Max Current per Phase (2 pumps running only)
22 Amps
Min Circuit Size (per phase)
150 Amps
Approx Weight Empty
1400 kg
Approx Weight Full
1500 kg
Side Clearance
50 mm
Back Clearance
50 mm
Front Clearance
850 mm
Top Clearance
350 mm