Tankpak
Model Number: Tankpak TP10
Rheem Tankpak Series is the next phase in commercial water heating, combining the benefits of mains pressure and continuous flow water heating.84% thermal efficiency heat source 6 Star heat source
- Vitreous enamel storage tank up to 82°C operation
- Large flow 50mm storage tank fittings
- Digital temperature display
- Fully hot dip galvanised frame with Tankpak 2-18
How it works
The thermostat senses the water in the storage tank and activates the primary pump which in turn activates the continuous flow water heaters. Water is drawn from the
bottom of the tank and is returned to the hot water outlet at the top of the tank. When the thermostat senses water in the tank at set point the pump and water heaters are turned off.
Top Down Heating
Rheem Tankpak utilises the top down heating principle. This allows the coldest water to be supplied to the continuous flow water heaters for the longest period of time to maximise the recovery rate whilst providing hot water immediately for use.
Other systems utilise a traditional return fitting on the storage tank which provides warmer water to the continuous flow water heater. This causes the water heaters to modulate the gas input and reduce the effective recovery rate.
Range
Rheem Tankpak is available from 1 to 10 Continuous Flow Water Heaters (CFWH) with 1 or 2 storage tanks depending on system size. Larger systems are available on application. Indoor or outdoor CFWH are assembled in banks from 2 to 6 by the installer, available in natural gas or LPG. Please note for systems greater than 6 CFWH the manifolds must be interconnected on site using equaflow.
Features Include:
- 82% thermal efficiency heat source
- Vitreous enamel storage tank up to 82oC operation
- Large flow 50mm storage tank fittings
- High storage tank delivery rating due to top down heating
- Digital temperature display
- Indoor and outdoor models available
- Pre-designed CFWH banks
Benefits Include:
- Mains pressure performance
- Reduced footprint
- High recovery
- Redundancy backup
Tankpak Typical Installation
Typical Installation with TP03 shown

| TANKPAK TECHNICAL DATA | ||||||||
| Model |
No. CFWH |
Thermal Input (MJ/h) |
Recovery @ 50oC Rise (L/hr) |
Storage Tanks |
1st Hour Delivery (L) |
Pump Model |
Pump Part Number |
Weight25 (kg) |
|
TPI01 TPE01 |
1 | 205 | 803 | 610340 | 1063 | UPS32-80N | 56959091UN | 122 |
|
TPI02 TPE02 |
2 | 410 | 1606 | 610340 | 1866 | CM 3-2 | 366084 | 203 |
|
TPI03 TPE03 |
3 | 615 | 2409 | 610340 | 2669 | CM 3-2 | 366084 | 228 |
|
TPI04 TPE04 |
4 | 820 | 3213 | 610340 | 3473 | CM 3-2 | 366084 | 293 |
|
TPI05 TPE05 |
5 | 1025 | 4016 | 610430 | 4344 | CM 5-2 | 366089 | 340 |
|
TPI06 TPE06 |
6 | 1230 | 4819 | 610430 | 5147 | CM 5-2 | 366089 | 365 |
|
TPI07 TPE07 |
7 | 1435 | 5622 | 2x 610340 | 6142 | CM 5-2 | 366089 | 510 |
|
TPI08 TPE08 |
8 | 1640 | 6425 | 2x 610340 | 6945 | CM10-1 | 366094 | 580 |
|
TPI09 TPE09 |
9 | 1845 | 7228 | 2x 610430 | 7748 | CM10-1 | 366094 | 647 |
|
TPI10 TPE10 |
10 | 2050 | 8032 | 2x 610430 | 8688 | CM10-1 | 366094 | 672 |
24 For systems using more than six CFWH each manifold assembly must be plumbed in parallel.
25 Weight includes CFWH unit, storage tank, pump and assumed likely weight of frame and manifolds.
NB: TPI = Internal, TPE = External