“Raypak® is a compact, efficient heating design which is the ideal way to heat large quantities of water for both hot water and hydronic applications.

The use of direct fired pure copper finned heat exchangers has been well proven over time.

And in the past fifty years, the Raypak® range has developed the high input water heater even further.”

Installation Energy
Indoor Gas

Product Specifications

DIMENSIONS AND TECHNICAL DATA TABLE – INDOOR/OUTDOOR MODELS
Natural – Input
– Output
MJ/h
kW
1,719
380
LPG – Input
– Output
MJ/h
kW
1,581
350

Dimensions
A
B
G
Flue Connection


mm
mm
mm
mm


2,060
2,070
930
455

Weight kg 440
Inlet/Outlet Connections   RC21/2/65
Gas Connection
Natural – On / Off Models
Natural – Modulating Models
LPG – On / Off Models
LPG – Modulating Models
 


R2/50
R2/50
R11/2/40
R1/25

Relief Valve Connection
On/Off models
Modulating models
 
RC3/4/20
RC1/25
Electrical Rating 240V 50Hz Watts
Amps
100
0.42
Min. Buffer Tank Capacity Litres 650
Max. Storage Capacity Litres 19,500
Natural Gas    
Litres Recovery Per Hour @ 30°C rise 10,893
  40°C rise 8,170
  50°C rise 6,536
  60°C rise 5,447
  65°C rise 5,028
  70°C rise 4,669
  75°C rise 4,357
  80°C rise 4,085
  85°C rise 3,845
Flow Rate and Pressure Drop
Max. Flow Rate
Modulating (10°C Rise)*
Pressure Drop

 

L/s
kPa

 

6.31
55

Max. Flow Rate
On/Off (15°C Rise)*
Pressure Drop

L/s
kPa


6.05
51

Min. Flow Rate
(20°C rise)*
Pressure Drop

L/s
kPa

4.54
30

 

GAS PRESSURE  
Natural Minimum kPa 1.10
  Test Point kPa 0.92
  Maximum kPa 4.00
LPG Minimum kPa 2.75
  Test Point kPa 2.75
  Maximum kPa 4.00
THERMOSTAT SETTINGS  
Modulating Maximum °C 95
  Factory set °C 78
  Minimum °C 44
On/Off Maximum °C 80
  Factory set °C 50
  Minimum °C 44
17CLEARANCES COMBUSTIBLES (mm)
Back Front Left Right Ceiling
600 750 600 600 1,200
17CLEARANCES NONCOMBUSTIBLES (mm)
Back Front Left Right Ceiling
150 750 300 300 1,200
Raypak® indoor gas water heaters are designed for connection to a flue system in accordance with the requirements of AS/NZS 5601.1.

18 Expansion Control Valve is not supplied with the water heater.
19 Figures in brackets are to be used if a Raypak stainless steel storage tank is utilised in the system.
20 An 850kPa relief valve can be fitted to modulating water heaters used in potable hot water applications.

ACCESSORIES FOR RAYPAK COMMERCIAL GAS WATER HEATERS
Accessories Standard Optional
Pump Run on Timer  modulating On/Off
Tankstat -
Hot Surface Ignition (HSI) - -
Electronic Ignition -
Water Flow Switch -
Relay Run and Fault Status -
Temperature and/or Pressure Gauge
(modulating burner models only)
-
Temperature Gauge (on/off models only) -
High Wind Top (outdoor installations only)
Rear Water Connections - -
Left Hand Water and Gas Connections -
Right Hand Water Connections - -
Right Hand Water and Gas Connections -
Audible Alarm -
Ambient Air Sensor
(modulating burner models only)
-
MINIMUM SUPPLY PRESSURE
System design and pump selection is critical when water heaters are connected to a low pressure water supply. Refer to the table below for minimum pressure equirements for Grundfos UPS series pumps. Minimum pressure requirements for TP series pumps depend on system characteristics and need to be calculated. Contact your pump supplier for details.
Pump Minimum Inlet Pressure Required (m)
at Operating Temperature
  75°C 80°C 85°C 90°C 95°C
UPS50-120B 4.0 5.0 6.0 7.0 9.0
WATER SUPPLY AND RELIEF VALVE SETTINGS
Burner Type   On/Off Modulating
Relief Valve Setting
Potable Hot Water
Mechanical Heating

kPa
kPa

850 (700)19
-

850 (700)19,20
415
Expansion Control Valve (ECV18) Setting
Potable Hot Water
Mechanical Heating

kPa
kPa

700 (550)19
-

700 (550)19,20
-
Maximum Supply Pressure without ECV18
Potable Hot Water
Mechanical Heating
fitted
kPa
kPa

680 (550)19
-

680 (550)19,20
330
with ECV18 fitted
Potable Hot Water
Mechanical Heating

kPa
kPa

550 (450)19
-

550 (450)19,20
-
RAYPAK MODEL NUMBERS
The following information should be supplied when ordering Raypak water heaters
B 0868 N C O / ID
Water
Heater
Approx
Thermal Input*
N = Natural Gas
P = Propane
Copper Heat
Exchanger
O = On/Off
M = Modulating
  ID = Indoor
OD = Outdoor
HWT = High Wind Top

Note: *last digit designates series type.

Technical Documents

Sample Specification View Online

Related Products

Model Number Location Hourly Thermal Input (MJ)
147 Indoor/Outdoor 144
200 Indoor/Outdoor 196
280 Indoor/Outdoor 278
350 Indoor/Outdoor 343
430 Indoor/Outdoor 420
507 Indoor/Outdoor 515
538 Indoor/Outdoor 539
658 Indoor/Outdoor 661
768 Indoor/Outdoor 765
868 Indoor/Outdoor 870
972 Outdoor 976
992 Indoor 999
1142 Outdoor 1142
1182 Indoor 1186
1242 Outdoor 1242
1292 Indoor 1289
1362 Outdoor 1357
1412 Indoor 1412
1662 Outdoor 1657
1852 Outdoor 1854
1922 Indoor 1926
2004 Outdoor 2004
2214 Indoor 2215
2404 Outdoor 2404
2634 Indoor 2636
2804 Outdoor 2804
3164 Indoor 3165
3304 Outdoor 3304
3694 Indoor 3692
3804 Outdoor 3804
4224 Indoor 4224