Heat Exchanger System 50-250kW
Model Number: 0191753 - 200kW
Typical applications include Co-gen and Tri-gen plants, process heating or as a separator in circuits employing PP-R piping.
- 5 models available 50, 100, 150, 200, 250kW
- WaterMark certified heat exchanger
- Manifold heat exchangers for greater output
- 316L stainless steel construction
- Single wall brazed plate heat exchanger
- Suitable for water to water only applications
- 1 year parts and labour
| Output (kW) | Flow Rate @ 20°C Rise (L/s) | Location | Warranty |
| 200 | 2.44 | Indoor/Outdoor | 1 year |
Product Specifications
| Non Potable Side | ||
| Inlet/Outlet Temperature | °C | 80/60 |
| Flow Rate | L/s | 2.44 |
| Pressure Drop | kPa | 6.98 |
| Potable Side | ||
| Inlet/Outlet Temperature | °C | 45/65 |
| Flow Rate | L/s | 2.43 |
| Pressure Drop | kPa | 6.91 |
| Dimentions | ||
| L x W x D | mm | 287x117x277 |
| Connections | Male | G1 1/4 |
| Weight | kg | 15 |
| Operating Pressure | kPa | 3000* |
| Electrical Supply (Temperature Controller) | 230-240V 50/60Hz Hard Wired by Electrician | |
*Maximum pressure will be governed by the lowest pressure appliance connected. The potable side must be run at higher pressure than the non potable side.
Technical Documents
| Owners Guide & Installation Instructions | Download |
| Brochure | Download |
| Heat Exchanger x 1 - 1 x Tank schematic.pdf | Download |
| Heat Exchanger x 1 - 1 x Tank schematic.dwg | Download |
| Heat Exchanger x 2 - 2 x Tank - 2 x Pump schematic.pdf | Download |
| Heat Exchanger x 2 - 2 x Tank - 2 x Pump schematic.dwg | Download |




.jpg)